Isolated Signal Conditioner:Function Modules:Limiter
MS3700 SeriesMS3714
Plug-in Type
Limiter
Converts DC current or voltage signals into commonly used DC signals and limits the outputs to force them to fall within the range between user-defined upper and lower limits.
4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V 0 to 10mV ±10V ±5V ±1V 0 to 1V 0 to 100mV and others
Output 2
4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V 0 to 10mV ±10V ±5V ±1V 0 to 1V 0 to 100mV and others
Response Time
400mse max.
Isolated Signal Conditioner:Sensor Signal Conditioners:CT Transmitters
MS3700 SeriesMS3720-01
Plug-in Type
Fast-Response CT Transmitter Average value calculation type
Calculates the rms values of AC current signals from a CT and converts them into commonly used DC signals. This model features a fast response time of 20ms or less (0 to 90%).
4 to 20mA 0 to 20mA 1 to 5mA 10 to 50mA 1 to 5V 0 to 10V ±10V ±5V 0 to 5V 0 to 1V and others
Output 1
4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V 0 to 10mV ±10V ±5V ±1V 0 to 1V 0 to 100mV and others
Output 2
4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V 0 to 10mV ±10V ±5V ±1V 0 to 1V 0 to 100mV and others
Response Time
80μ/150μsec max.*
Isolated Signal Conditioner:Frequency Converters:Pulse Shapers (Pulse Isolators)
MS3700 SeriesMS3749
Plug-in Type
High-Frequency Pulse Shaper (Pulse Isolator)
Slim, plug-in high frequency pulse shaper that accepts pulse train signals from sensors or other devices and shapes these pulses or converts signal levels, and provides isolated single or dual output.
Dry contact, open collector (pull-up: approx. 12V, 3.3kΩ), AC voltage pulse (threshold voltage: approx. 0.06Vp-p), DC voltage pulse (threshold voltage: approx. 2V), 4 to 20mA DC pulse (threshold current: approx. 8mA), line driver pulse (receiver equivalen)
Output 1
TTL level, open collector, voltage pulse 10V+/-10%, voltage pulse 12V+/-±10%
Output 2
Line driver pulse (RS-422 driver output)
Isolated Signal Conditioner:Frequency Converters:Pulse to Relay Contact Converter
MS3700 SeriesMS3759
Plug-in Type
Pulse to Relay Contact Converter
Converts pulse train signals into relay contact (form A or C contact) signals.
4 to 20mA 0 to 20mA 1 to 5mA 10 to 50mA 1 to 5V 0 to 10V ±10V ±5V 0 to 5V 0 to 1V and others
Output 1
4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V 0 to 10mV ±10V ±5V ±1V 0 to 1V 0 to 100mV and others
Output 2
4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V 0 to 10mV ±10V ±5V ±1V 0 to 1V 0 to 100mV and others
Response Time
85ms max. High-speed response type 10ms max
Isolated Signal Conditioner:Math Computation Modules:Subtractors
MS3700 SeriesMS3762F
Plug-in Type
Subtractor (Fast Response Model)
Receives two DC current or voltage signals and outputs a signal proportional to the difference of those signals. This model features a fast response time of 400μsec (0 to 90%).
The MS3700 Series features 29 mm slim design, plug-in connection, wide-range AC power input, high accuracy and durability, and a 7-year warranty, the longest in the industry.
Slim plug-in design for easy maintenance
Standard series, featuring the largest model line-up among all our series
Function modules, alarm setters, math computation modules, and programmable models are available.*2
DIN rail / wall mounting
A total of 46 models
A wide range of applications from a single to multiple use
*1 Non-isolated I/O models (2-way isolation) are available. Please refer to the relevant product specification sheet.
*2 Programmable models are only MS3768 and MS377□.
*3 Products are warranted for years from the date of shipment.
*4 This feature is limited to some models, so please check our model list.
The MS3700 Series is a line of slim signal conditioners (size: W29 × H86 × D125 mm, including the socket) that offers isolated single or dual output with high reliability and high accuracy.
Conformal coating
Coating is not only resistant to accidental exposure to corrosive gas or oily smoke, but has a number of benefits contributing to long-term reliability. It avoids direct exposure to air to protect printed circuit boards and electronic parts against humidity, moisture, dust, chemicals, and thermal stress, thereby preventing corrosion, migration and any other damages. (HumiSeal® 1A27NSLU is used as a conformal coating. ) * This will be optional at extra cost, starting with orders placed on November 1, 2022.
Gold-plated contact parts
To achieve high reliability and durability, the contact parts of the main unit and socket are plated with gold of 0.2 μm in thickness. This prevents not simply wear caused by insertion and removal of the unit, but contact degradation even in harsh environments to ensure high reliability for a long period.
Drop-proof screws employed
The screws employed eliminate the need to care about dropping them during the wiring work. Besides, the M3.5 screws are one size larger than those for competitive products of the same grade, which makes field wiring much easier.
Ceramic capacitors employed
This series employs ceramic capacitors to achieve low current draw with extremely low heat generation, thus leading to long service life.
(The ceramic capacitors are not affected by prolonged use, as opposed to aluminum electrolytic capacitors.)*5 。
Multi-turn trimmers employed
This series employs multi-turn trimmers for zero and span adjustments. Our conventional series have used 3-turn or 4-turn trimmers, but the multi-turn trimmers employed facilitate fine adjustment and provide improved resistance to vibration. The new trimmers also have static protection.
Close mounting
The MS3700 Series design is such that the width of the socket is 4 mm (2 mm each side) larger than that of the main unit. Even if you mount two or more sockets side by side, there should always be a clearance between the modules, thereby preventing a rise in temperature around them.
Socket provided with a power terminal block cover as standard
For safety reasons, the socket is provided with a power terminal block cover as standard.
Equipped with set value indicator LED
Several models, including ratio/bias converters, alarm setters and a manual setter, are equipped with a set value indicator LED.*6
Set values are adjustable with the front accessible switches
For user-configurable signal conditioners, including function modules, math computation modules and alarm setters, the factors or alarm settings can be easily changed only with the front-accessible switches. No hand-held terminal required. Simple to use and efficient!
Distributor provided with a transmitter power supply switch
The 3707 distributor (with isolation) has a transmitter power supply switch on its front panel. Turning this switch off allows the distributor to be used as an isolator for adjustment. If you have not yet decided whether to use a distributor or an isolator at the design phase, you should select this model so that it can be used for both applications.
(Note that the terminal connections are different depending on whether the unit is used as a distributor or an isolator.)
(The non-isolated model, MS3737 also includes a transmitter power supply switch.)
*5 DC powered: No aluminum electrolytic capacitors or tantalum capacitors used.
AC powered: Aluminum electrolytic capacitors are partly used in the power section.
*6 User-configurable models, including function modules and math computation modules, only.
Module Specifications
Wiring
M3.5 screw terminal connection (with a power terminal block cover & drop-proof screws)
Materials
Housing and Socket
ABS resin (UL 94V-0)
Screw Terminal
Nickel-plated steel
Surface Treatment for Plugs and Receptacle Holes
Brass with 0.2 µm gold plating
PCB
Glass fabric epoxy resin (FR-4: UL 94V-0)
Conformal Coating
HumiSeal® 1A27NS (Polyurethane) * This will be optional at extra cost, starting with orders placed on November 1, 2022.
Isolation
3-way (single output) or 4-way (dual output) isolation between input, output 1, (output 2), and power.*
Insulation Resistance
100Ω min. (@ 500V DC) between input, output 1, (output 2), power, and ground.*
Dielectric Strength
2000V AC for 1 minute between input, output 1, (output 2), power, and ground.*
Power Specifications
Power Requirements
85 to 264V AC: Rating 100 to 240V AC (47 to 63 Hz)
24V DC ± 10%
85 to 264V DC: Rating 100 to 240V DC
Overcurrent Protection
160 mA fuse
Installation Specifications
Operating Temperature Range
-5 to 55℃
Operating Humidity Range
5 to 90% RH (no condensing)
Storage Temperature Range
-10 to 60℃
Installation
Wall/DIN rail mounting
Dimensions
W29 × H86 × D125 mm (including the mounding screw and socket)
Weight
Main Unit
120g max.
Socket
80g max.
*Non-isolated models are available. Please refer to the relevant product specification sheet.